UPS Operation
For detailed operational procedures on the Hitzinger UPS, please Contact Us. Our systems operate based on five simple steps, as detailed below,

-
Diesel engine Starts
-
By-pass switch shuts down (Mains-synchronised)

-
The choke provides the consumer‘s and the synchronous machine‘s mains power supply
-
Kinetic Module stores Kinetic energy
-
Synchronous machine provides un-fluctuating consumer‘s voltage and supply of reactive power
-
Filtering and balancing of upper harmonics and asymmetry
-
Supply of non-critical consumers directly via the mains, Distortion factor < 3%

-
Mains power switch opens
-
KIN module provides the UPS load uninterruptedly
-
Start of the diesel engine
-
Acceleration until the rated speed is reached
-
When the rated speed is reached, the diesel engine provides the UPS supply and charges the KIN module (frequency drop ≤ 1%)

-
Re-synchronisation of the consumer load
-
Opening of the clutch
-
Switching off of the engine after determined cooling-off period (via engine fan or separated 2-stage electrical fan)

-
When Mains power is available, the main power switch closes
-
Diesel engine turns off
-
The choke provides the consumer‘s mains power supply
-
Synchronous machine provides un-fluctuating consumer‘s voltage and supply of reactive power
-
Supply of non-critical consumers directly via the mains, Distortion factor < 3%